Inspection History: FIRE - ALARM FINAL

Permit Number - T15BU00911

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
01/28/2016 FIRE - ALARM FINAL Partial Approval System Tested and signals verified. Passed test.
STILL NEED:
1. Points must match the plans ( points are zones)
2. Must submit as builds that reflect added appliances and appliances not added as per plan. Two versions of plan ( no Revision written on them - neither match actual install).