Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG PIPING FLUSH
Permit Number - T15BU00896
Inspection Description - FIRE SPKLR - UG PIPING FLUSH
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2015 | FIRE SPKLR - UG PIPING FLUSH | Approved | Flushed 3 times for 1 minute. First with Burlap - some debris second without burlap, one minute more. Third with burlap - ran clean 1 minute, no debris in bag. Approved. |
|
08/12/2015 | FIRE SPKLR - UG PIPING FLUSH | Denied | Not done due piping not connected to riser | |
08/10/2015 | FIRE SPKLR - UG PIPING FLUSH | Denied | STILL NEED FLUSHING | |
08/06/2015 | FIRE SPKLR - UG PIPING FLUSH | Denied | No flush will be performed until the underground has been exposed for inspection. |