Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG PIPING FLUSH
Permit Number - T15BU00896
Inspection Description - FIRE SPKLR - UG PIPING FLUSH
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/19/2015 | FIRE SPKLR - UG PIPING FLUSH | Approved | Flushed 3 times for 1 minute. First with Burlap - some debris second without burlap, one minute more. Third with burlap - ran clean 1 minute, no debris in bag. Approved. |
|
| 08/12/2015 | FIRE SPKLR - UG PIPING FLUSH | Denied | Not done due piping not connected to riser | |
| 08/10/2015 | FIRE SPKLR - UG PIPING FLUSH | Denied | STILL NEED FLUSHING | |
| 08/06/2015 | FIRE SPKLR - UG PIPING FLUSH | Denied | No flush will be performed until the underground has been exposed for inspection. |