Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
Permit Number - T15BU00893
Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2015 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | 200 PSI FOR 2 HOURS | |
08/21/2015 | FIRE SPKLR - UG, PIPING, HYDRO | Denied | Misscommunication about time system was pressured up and pressure was released before 2 hrs. Held 200 for 1/5 hrs. Must recharge the system to 200 psi for 2 hrs and then the persons pump broke and could not recharge today. Will do Monday and call it in. | |
08/06/2015 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | Only called for site on piping so they can bury piping before rain, thrust blocking in place, tracer wire in place, depth 30" to 40" deep and all metal wrapped with plastic PVC wrap. (T14CM08825) Okay to bury all unground pipe Still need to do 200 PSI test for 2 hours and flush using a burlap to make sure no foreign material is in piping. |