Permit: T15BU00893

Parcel: 134234130


Addresses:

245 S WILMOT RD


Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Permit Number - T15BU00893

Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
08/24/2015 FIRE SPKLR - UG, PIPING, HYDRO Approved 200 PSI FOR 2 HOURS
08/21/2015 FIRE SPKLR - UG, PIPING, HYDRO Denied Misscommunication about time system was pressured up and pressure was released before 2 hrs. Held 200 for 1/5 hrs. Must recharge the system to 200 psi for 2 hrs and then the persons pump broke and could not recharge today. Will do Monday and call it in.
08/06/2015 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval Only called for site on piping so they can bury piping before rain, thrust blocking in place, tracer wire in place, depth 30" to 40" deep and all metal wrapped with plastic PVC wrap. (T14CM08825)
Okay to bury all unground pipe
Still need to do 200 PSI test for 2 hours and flush using a burlap to make sure no foreign material is in piping.