Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2015 | FIRE - ALARM FINAL | Approved | ||
| 08/18/2015 | FIRE - ALARM FINAL | Denied | Tested the monitoring system all passed except the following: 1. All duct smoke detectors shall be on the fire alarm monitoring system. IFC 907.3 & 907.3.1 2. Need lock outs on the breakers for the fire bell and fire alarm panel. 3. Need to label riser warning people servicing the riser that there is two alarm systems monitoring the riser. |