Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
| Date |
Description |
Inspector |
Results |
Comments |
| 08/14/2015 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Approved |
exposed joints and tracer wire was on pipe. call for flush when connection made. |
| 08/12/2015 |
FIRE SPKLR - UG, PIPING, HYDRO |
|
Partial Approval |
200 psi for 2 hours was done but could not find tracer wire and piping was covered up with mud from rain storm, need to uncover and add tracer wire. |