Permit: T15BU00885

Parcel: 110120910


Addresses:

2695 N CRAYCROFT RD


Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T15BU00885

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2015 FIRE - KITCHEN EXH HOOD FINAL Approved
09/08/2015 FIRE - KITCHEN EXH HOOD FINAL Denied 1. Changed from a 3 gal and 1.5 gal to 2-3 gal tanks. Changed 2 - 1 N nozzles over range to 3 - 1 F nozzles ( appropriately distanced and positioned). Direction of 1 N Nozzles in plenum is reversed - coverage is withing acceptable limits though. Submit As builds for approval.
2. Hood Suppression System not hooked up to fire alarm system.
3. Distance between the 3 N nozzles over the the braiser are at 40 " high and must be between 25 - 35 inches.
System DID PASS - cut link, pull station, electric and gas shutdown and exhaust stayed on. No make up air is connected to the hood.
Just need to test to see if alarm sounds and reports when hood is activated.
NS
09/03/2015 FIRE - KITCHEN EXH HOOD FINAL Cancelled