Permit: T15BU00836

Parcel: 13502134B


Addresses:

6970 E 22ND ST #100


Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T15BU00836

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2016 FIRE - KITCHEN EXH HOOD FINAL Approved New Detection Line installed. Link test - passed. Pull station has been moved down to 48 inches in height.
03/21/2016 FIRE - KITCHEN EXH HOOD FINAL Denied 1. Detection line coated in grease. When doing the link test, the cble inside the conduit di not move at all. Must replace the entire detection line.
2. Must move the pull station - it is currently at 60 inches and may be no higher than 48 inches.

Precitation for 48 hrs was issued to replace detection line and clean ventilation from filter to roof. Last maintenance until this modification was over a year ago. Frequency of cleaning shall be at 3 month intervals per 2012 IFC 609.3.3.1
PASSED the 'puff' test - pull station initiated cartridge and all caps blew off over cook line. Gas valve shut off. Exhaust remained on. There is no make up air. All nozzles are correct and at proper distance. 4th appliance in from Left is not a WOK, it is a boiling pot. It does not need coverage, but the owner is going to leave the 260 nozzle in place. Points match supply capacity of 9 lbs ( 3 bottles).
03/08/2016 FIRE - KITCHEN EXH HOOD FINAL Not ready for Inspection Metro unable to come down from phoenix, will reschedule for next week.
09/15/2015 FIRE - KITCHEN EXH HOOD FINAL Cancelled WILL WAIT FOR MECHANICAL FINAL AND APPLICANT WILL CALL IN FOR NEXT DAY IF MECHANICAL PASSES