Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T15BU00826
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2015 | FIRE SPKLR - FINAL | Approved | ||
08/21/2015 | FIRE SPKLR - FINAL | Denied | 1. In family lounge in South East corner 1 head is 10 feet off the wall. 2. File Room is not a light hazard area ( sprinklers are 8 feet off 1 wall) 3) Sewing Shopping missing 1 head West Wall, South Side (between work shop and rest room). 4) Far ulitility room on NW corner of building other side of training room. This room has been extended and there are no heads. Heads near curtain wall are fine ( when closed it would be a light hazard room under 800 square feet and there for the heads can be 9 feet off one wall ( the curtain wall). Heads that are 8 feet off wall in family lounge are fine ( light hazard area). |