Inspection Status: Approved
Inspection History: FIRE SPKLR - UG PIPING FLUSH
| Date |
Description |
Inspector |
Results |
Comments |
| 07/27/2015 |
FIRE SPKLR - UG PIPING FLUSH |
|
Approved |
Flushed for 1 min |
| 07/17/2015 |
FIRE SPKLR - UG PIPING FLUSH |
|
Denied |
Tried to use a 'lay flat 6 inch hose connected at the stub up and then connected to a 4 inch pipe out to parking lot. the flat hose reduced the width under 4 inches at the 90 degree bend. Need to use a hard pipe ( no less than 4 inches) to flush. Will call in next week. |