Permit: T15BU00789

Parcel: 13423411C


Addresses:

6352 E BROADWAY BL

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG PIPING FLUSH

Date Description Inspector Results Comments
07/27/2015 FIRE SPKLR - UG PIPING FLUSH Approved Flushed for 1 min
07/17/2015 FIRE SPKLR - UG PIPING FLUSH Denied Tried to use a 'lay flat 6 inch hose connected at the stub up and then connected to a 4 inch pipe out to parking lot. the flat hose reduced the width under 4 inches at the 90 degree bend. Need to use a hard pipe ( no less than 4 inches) to flush. Will call in next week.