Permit: T15BU00789

Parcel: 13423411C


Addresses:

6352 E BROADWAY BL

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Date Description Inspector Results Comments
07/17/2015 FIRE SPKLR - UG, PIPING, HYDRO Approved Held pressure from 7 am to 9:30 am ( 210 psi at read).
no leaks. 6 inch pipe with megalug connections. Nuts broke off and in pit , joints wrapped. May back fill.