Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
Permit Number - T15BU00789
Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/17/2015 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | Held pressure from 7 am to 9:30 am ( 210 psi at read). no leaks. 6 inch pipe with megalug connections. Nuts broke off and in pit , joints wrapped. May back fill. |