Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/22/2015 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 07/21/2015 |
MECHANICAL - FINAL |
|
Partial Approval |
REPAIR BROKEN ELEC CONDUITS ON ROOF AT CONNECTION TO DISCONNECT. PROVIDE A DRAIN ON LARGE FAN. INTERLOCK MAKE UP AIR WITH EXHAUST FAN. |