Permit: T15BU00751

Parcel: 130144550


Addresses:

4426 E 22ND ST


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T15BU00751

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/29/2015 FIRE - ALARM FINAL Approved
10/28/2015 FIRE - ALARM FINAL Partial Approval must submit as builds with added devices and upsized batteries
10/13/2015 FIRE - ALARM FINAL Partial Approval Passed: 1) smoke, pull at panel - signals recieved alarm
2) tested 10% duct detectors and recieved copy of 3rd party acceptance test of all duct detectors.
3) 2 flow tests on 2 seperate risers - signals reported & shut big ass fans ( signals recieved - supervisory).
4) 3 Tampers ( main, office, service) - signals recieved as supervisory.
Still need: Hook up smoke and heat detectors in elevator
3 duct detectors in trouble mode.