Inspection History: FIRE - ALARM FINAL

Permit Number - T15BU00656

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/31/2015 FIRE - ALARM FINAL Approved Signals sent and received.
12/30/2015 FIRE - ALARM FINAL Denied DENIED BECAUSE SIGNALS NOT BEING RECEIVED BY MONITORING COMPANY ( ALARMS, TROUBLES AND SUPERS).
MUST SUBMIT AS BUILDS TO REFLECT ADDITION OF PULL STATION ( NO REDLINES ACCEPTED).

What HAS passed:
All notification appliances ( strobes and horn strobes) tested and operational and installed per approved plans. Trouble received at the panel when EOL removed on both NAC1 and NAC2.
Circuit 11 is locked out.
Panel receiving all signals.