Permit: T15BU00623

Parcel: 14102013F


Addresses:

9455 E VALENCIA RD

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
12/21/2015 FIRE SPKLR - OH PIPING & HYDRO Approved approved. see records.
10/05/2015 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 200 PSI and inspection for the mezzanane only
09/16/2015 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. passed pressure test - 220 psi for nearly 24 hrs
2. mezzanane not framed out yet, so that line has yet to be installed.
09/11/2015 FIRE SPKLR - OH PIPING & HYDRO Partial Approval removed head that was within 6 ft in mens rest room.
09/10/2015 FIRE SPKLR - OH PIPING & HYDRO Partial Approval added head btwen duct work in ceiling over womens room.

The head added in the mens room is within 6 ft of another head and flex duct work is lower so that the heads will now 'see' eachother and possibly cold solder one another. Keep flex duct work lower than heads so pattern is not blocked and cap off newly installed upright so that the original heads on the plans will be sufficient.
NS
09/04/2015 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1.Need 1UR head btween ducts in womens room.
2.Need 1 UR head bteen flex duct and North most head in mens restroom.
07/02/2015 FIRE SPKLR - OH PIPING & HYDRO Partial Approval IVRS - Inspection :*
07/02/2015 FIRE SPKLR - OH PIPING & HYDRO Partial Approval For Classrooms...
HYDRO PASSED
Pressured up at 11:15 AM today.
Read at 1:34 PM - 210 psi
Overhead is a PARTIAL APPROVAL

1. 3 uprights need to be flipped to the NW to provide for no more than 7 feet 5 inches. See plans for details.