Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T15BU00616
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2016 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
04/29/2016 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Ok fo hydro in rear stock room. | |
04/14/2016 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | ||
03/08/2016 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | This inspection is for "system 4" only. Hydro passed. Missing uprights above walk in coolers, bakery area, NW side. See plans. | |
08/26/2015 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Inspected pharmacy area only - 14 heads will be on static pressure so Wal-Mart can open the pharmacy by midnight tonight (see marked plans). STILL NEED TO DO A HYDRO PRESSURE TEST AT 200 PSI FOR 2 HOURS Contractors permit T14CM03195 |