Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T15BU00588
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2015 | FIRE - ALARM FINAL | Approved | ||
| 09/17/2015 | FIRE - ALARM FINAL | Denied | 1) Turn up speakers, carnival area. 2) Add lights above mazes x 2. Tie into system. 3) Need dedicated circuit for ACP. 4) I will research adding devices to outdoor corale area. 5) Add lights, outdoor bridge area. Tie into system. 6) All theatrical items shall shut off upon activation. Currently, none of the props shut down. |