Permit: T15BU00539

Parcel: 13321074A


Addresses:

6327 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T15BU00539

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/27/2015 FIRE - ALARM FINAL Approved
07/08/2015 FIRE - ALARM FINAL Partial Approval 1. Need to activate the alarm system to test delay by-pass on all exit doors that have the 15 second delay - need to make sure the delay shuts off and door operates with no delay.
2. All egress doors o that have delay egress operation shall have the following sign attached above the panic hardware device stating the following:
"PUSH UNTIL ALARM SOUNDSDOOR CAN BE OPEND IN 15 SECONDS" Lettering shall be at least 1 inch height and shall have a stroke of not less than 1/8 inch on a contrasting background.
3. Exit door by golf putting holes panic hardware failed to work on 15 second delay need to repair or replace