Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T15BU00539
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2015 | FIRE - ALARM FINAL | Approved | ||
07/08/2015 | FIRE - ALARM FINAL | Partial Approval | 1. Need to activate the alarm system to test delay by-pass on all exit doors that have the 15 second delay - need to make sure the delay shuts off and door operates with no delay. 2. All egress doors o that have delay egress operation shall have the following sign attached above the panic hardware device stating the following: "PUSH UNTIL ALARM SOUNDSDOOR CAN BE OPEND IN 15 SECONDS" Lettering shall be at least 1 inch height and shall have a stroke of not less than 1/8 inch on a contrasting background. 3. Exit door by golf putting holes panic hardware failed to work on 15 second delay need to repair or replace |