Inspection History: FIRE SPKLR - UG PIPING FLUSH

Date Description Inspector Results Comments
05/14/2015 FIRE SPKLR - UG PIPING FLUSH Approved fLUSHED FOR 1 MINUTE ( UNTIL CLEAR).
ALL CONNECTION ARE PER CODE. 225 PSI FOR 3.5 HOURS

MUST WRAP BEFORE BACKFILLING.
APPROVED.