Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/17/2015 |
FIRE SPKLR - FINAL |
|
Approved |
|
| 06/04/2015 |
FIRE SPKLR - FINAL |
|
Denied |
1. Still 19ft. gap between sprinkler heads at West wall. |
| 05/01/2015 |
FIRE SPKLR - FINAL |
|
Denied |
West wall has insufficient coverage. There is 19 feet between heads close to the wall ( look on plans) and the nearest head centered between them is 9 feet off the wall. Can not have more than 7.6 off wall being that heads are fusable links and not residential extended coverage. |