Permit: T15BU00437

Parcel: 117132170

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
06/17/2015 FIRE SPKLR - OH PIPING & HYDRO Approved
05/01/2015 FIRE SPKLR - OH PIPING & HYDRO Denied System is pressurized ( since Monday) and has no leaks.
Head spacing is not correct on West wall
there is a 19 foot gap between heads closest to the wall and the nearest head centere in between is 9 feet off the wall. ( look at plans).