Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - HYDRANTS
Permit Number - T15BU00427
Inspection Description - FIRE - HYDRANTS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/10/2015 | FIRE - HYDRANTS | Approved | Hydrant #7 flowed - passed | |
06/22/2015 | FIRE - HYDRANTS | Partial Approval | 1. Flowed water from the following fire hydrants number 1-2-3-4-5-6 out of seven, #7 was not turned on to test still need to flow water from #7. 2. 200 PSI for 2 hours (Hydro) test completed for buildings number 2-3-12-13-14 & clubhouse lines were buried did not see placement - all passed pressure test. Buildings number 10 & 11 according to the contractor they did not have the isolation valves and were not installed according to the approved plans NOT APPROVED. 3. Need to keep the access roads on property clear of mud, pot holes, construction equipment and building supplies at all times 24 hours a day. 4. OKAY TO BUILD ANYWHERE ON PROPERTY. |
|
06/01/2015 | FIRE - HYDRANTS | Partial Approval | Only one hydrant working by main entrance by old Spanish trail road (now being used for the water tanker), 300 feet TFD will allow construction of building #14 and club house only all combustible material needs to stay within the 300 feet hose lay from the hydrant. According to the contractor they will have all hydrants fully functional by next week. Still ned to flush lines |