Permit: T15BU00401

Parcel: 11012005A


Addresses:

2585 N WYATT DR


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T15BU00401

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/30/2015 FIRE SPKLR - FINAL Approved To clear permit
05/20/2015 FIRE SPKLR - FINAL Partial Approval Partial Approval given for phase #2 only as marked on approved plans - okay to use building
04/22/2015 FIRE SPKLR - FINAL Not ready for Inspection STILL HAVE ANOTHER PHASE; ADD SPRINKLERS TO THE NW SIDE OF NEW BUILDING.
NS
04/16/2015 FIRE SPKLR - FINAL Not ready for Inspection final was called in prematurely.
Overhead pressure test on addition to system passed ( 205 psi recorded at noon) was pressurized at 8:30 am
Checked all heads installed above and below. Upright in ceiling space on NE corner near the door was obstructed by flex duct work. Must be above duct work to have coverage of space. See plans for specific location.