Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Permit Number - T15BU00389

Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2015 FIRE SPKLR - UG, PIPING, HYDRO Approved Pressure tested before the flush. Was charged at 7 AM at 200 psi. Was still at 200 psi at 11:30 am this morning at test. Bled pressure off and prepared for flush.
NS
04/10/2015 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval 1. Partial for piping placement.
2. Still need Hydro.
3. Okay to backfill.