Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T15BU00363

Parcel: 125101480


Addresses:

3541 E BROADWAY BL

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
06/19/2015 FIRE SPKLR - OH PIPING & HYDRO Approved
06/17/2015 FIRE SPKLR - OH PIPING & HYDRO Partial Approval hydro test passed. Was charged to 200 psi at 6:00 AM. witnessed pressure of 220 psi by 1:30 PM.
STILL NEED:
1. add 3 heads ( 1 hydraulic calc zone)
2. replace 3 painted heads
3. move 1 head in mens dressing area.