Inspection Status: Partial Approval
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2015 | FIRE SPKLR - FINAL | Partial Approval | Revise plans were given to me on site need to check and approved them before final will be given. | |
| 06/16/2015 | FIRE SPKLR - FINAL | Denied | 1. Need fire bell wired 2. Need FDC changed out to a swivel type hose connection 3. Need as builts showing all changes from the approved plans (heads temp - location changes- adding heads) 4. Need new calculations because adding more heads in the calculated area |