Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T15BU00279
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2015 | FIRE SPKLR - FINAL | Approved | Coverage is now within limits ( no more than 7.5 off of a wall and both heads are no closer than 6 feet to each other and no more than 15 feet distance apart. | |
04/03/2015 | FIRE SPKLR - FINAL | Denied | 1. Need to move at least 1 head in Suite 1008. 2 heads are more than 7'6" off of more than 1 wall. |