Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/07/2015 |
FIRE SPKLR - FINAL |
|
Approved |
Coverage is now within limits ( no more than 7.5 off of a wall and both heads are no closer than 6 feet to each other and no more than 15 feet distance apart. |
| 04/03/2015 |
FIRE SPKLR - FINAL |
|
Denied |
1. Need to move at least 1 head in Suite 1008. 2 heads are more than 7'6" off of more than 1 wall. |