Inspection History: FIRE SPKLR - FINAL

Permit Number - T15BU00279

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2015 FIRE SPKLR - FINAL Approved Coverage is now within limits ( no more than 7.5 off of a wall and both heads are no closer than 6 feet to each other and no more than 15 feet distance apart.
04/03/2015 FIRE SPKLR - FINAL Denied 1. Need to move at least 1 head in Suite 1008. 2 heads are more than 7'6" off of more than 1 wall.