Permit: T15BU00261

Parcel: 14029050B

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
04/13/2015 FIRE SPKLR - FINAL Approved
04/02/2015 FIRE SPKLR - FINAL Denied The plans list the use of 155 degree heads under ductwork, but the new heads are green ( 200 dgree) heads. All other heads in the area are light hazard. Heads must be installed per the approved plans.
Denied.