Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2015 | FIRE SPKLR - FINAL | Approved | ||
| 04/02/2015 | FIRE SPKLR - FINAL | Denied | The plans list the use of 155 degree heads under ductwork, but the new heads are green ( 200 dgree) heads. All other heads in the area are light hazard. Heads must be installed per the approved plans. Denied. |