Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
Permit Number - T15BU00259
Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/17/2015 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | Ductile iron is covered, joints have megalugs ( felt under the plastic covering), 200 psi since 6 AM ( recorded at 10:26 AM), no leaks, built as per approved plans. City alread back filled over their where it ties into permitted portion. NS / 3/17/15 NS 3/17/15 |