Permit: T15BU00259

Parcel: 12810069C


Addresses:

436 S WILLIAMS BL

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Date Description Inspector Results Comments
03/17/2015 FIRE SPKLR - UG, PIPING, HYDRO Approved Ductile iron is covered, joints have megalugs ( felt under the plastic covering), 200 psi since 6 AM ( recorded at 10:26 AM), no leaks, built as per approved plans. City alread back filled over their where it ties into permitted portion.
NS / 3/17/15
NS 3/17/15