Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2015 | FIRE - ALARM FINAL | Approved | All horn / Strobes are operating Batteries passed 24 hr test - Alarm system returned to AC power and locked out. Supervisory signal now being received when Sprinkler Valve is Shut off. Approved... NS 7/1/15 |
|
| 06/30/2015 | FIRE - ALARM FINAL | Denied | 1. Some horn strobes were not working. 2. Permforming 24 hr test on batteries starting this afternoon. |