Inspection History: FIRE SPKLR - FINAL
Permit Number - T15BU00191
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/28/2015 | FIRE SPKLR - FINAL | Approved | ||
02/24/2015 | FIRE SPKLR - FINAL | Denied | 1. WMG failed to work need to repair or replace WMG (water motor gong) 2. FDC (fire department connection) is behind gated fence need to move FDC outside of fencing area 3. Need to install a sign above or next to new FDC the, sign shall be made up with a red background with white lettering stating the following; "FDC (6 inch size letters) 3850 & 3870 N. Oracle (2" size letters). 4. Need to paint the new supply piping to protect from weather 5. Need 5yr check valve inspection completed 6. Need fire department key box installed and a key inside for access to fenced in riser area. |