Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T15BU00176
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2015 | FIRE SPKLR - FINAL | Approved | Mono kote is on the I beam above drop ceiling and on beam that t-s off from it. Sprinklers over light hazard area are approved. Head was added for wall coverage on NE corner. Uprights in back approved. 1 added under duct work ( wider than 4 feet). Approved. |
|
03/11/2015 | FIRE SPKLR - FINAL | Partial Approval | Checked sprinkler piping for upright coverage okay to install drop ceilings and hard lids. |