Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/19/2015 |
FIRE SPKLR - FINAL |
|
Approved |
|
| 03/11/2015 |
FIRE SPKLR - FINAL |
|
Partial Approval |
Checked sprinkler upright coverage found problems, need to correct front part of the store, uprights over 225 coverage 120 is not needed due to area is noncombustible unobstructed per table 8.6.2.2.1.(a) NFPA 13 2013ED. Okay to install drop ceilings and hard lids need to keep some ceiling tiles to check upright coverage when corrected. |