Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T15BU00175
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/19/2015 | FIRE SPKLR - FINAL | Approved | ||
03/11/2015 | FIRE SPKLR - FINAL | Partial Approval | Checked sprinkler upright coverage found problems, need to correct front part of the store, uprights over 225 coverage 120 is not needed due to area is noncombustible unobstructed per table 8.6.2.2.1.(a) NFPA 13 2013ED. Okay to install drop ceilings and hard lids need to keep some ceiling tiles to check upright coverage when corrected. |