Permit: T15BU00175

Parcel: 12801005H

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T15BU00175

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/19/2015 FIRE SPKLR - FINAL Approved
03/11/2015 FIRE SPKLR - FINAL Partial Approval Checked sprinkler upright coverage found problems, need to correct front part of the store, uprights over 225 coverage 120 is not needed due to area is noncombustible unobstructed per table 8.6.2.2.1.(a) NFPA 13 2013ED. Okay to install drop ceilings and hard lids need to keep some ceiling tiles to check upright coverage when corrected.