Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T15BU00086
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/24/2015 | FIRE - ALARM FINAL | Approved | ||
11/20/2015 | FIRE - ALARM FINAL | Partial Approval | flow - 40 seconds all pulls ( 4) working and reporting signal correctly all smokes ( 6 ) working and 5 reported signal correctly. ( comm room smoke reported incorrect zone) tamper switch worked but reported the wrong zone battery diconnect - trouble AC out - trouble breaker is locked out |