Permit: T15BU00075

Parcel: 110120910


Addresses:

2695 N CRAYCROFT RD


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T15BU00075

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/15/2015 FIRE - ALARM FINAL Approved
06/05/2015 FIRE - ALARM FINAL Not ready for Inspection NORM CALLED AND STATED THAT THE PANEL IS STILL MISCOMUNICATING WITH THE PANEL AT TMC AND THAT THEY WERE NOT YET READY FOR INSPECTION.
06/04/2015 FIRE - ALARM FINAL Denied 1. Must submit as builds.
2. Must fix alarm issues with how the duct detectors are reporting to the proprietary monitor at TMC. Half reported as alarm and half as trouble. Should be supervisory.
3. Also, the pull station sounded a local alarm that reported to the panel on site, but was not received at TMC's panel.
What Passed -
All duct detectors were set off by smoke.
Both the Lobby Main and the IOP entrance doors auto unlocked when the pull station was pulled.
06/01/2015 FIRE - ALARM FINAL Denied 1. Tested 4 air handlers duct detectors failed to stay in the latch position. All air handlers to be set as latch and stay latched until reset is done at the FACP. All 4 air handlers started automatically without the reset.
2. Need to clear DACT #1 and #2 troubles on panel
3. Need to clear LCD 7100 #5 trouble from panel
4. Need to have a clear panel before final will be given
5. Need as bults for the following: labeling changes, pull stations remove, annunciator panel's new locations, strobe removed.
6. Corridor #130 horn/strobes are not synchronized.
05/28/2015 FIRE - ALARM FINAL Cancelled