Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T15BU00075
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/15/2015 | FIRE - ALARM FINAL | Approved | ||
06/05/2015 | FIRE - ALARM FINAL | Not ready for Inspection | NORM CALLED AND STATED THAT THE PANEL IS STILL MISCOMUNICATING WITH THE PANEL AT TMC AND THAT THEY WERE NOT YET READY FOR INSPECTION. | |
06/04/2015 | FIRE - ALARM FINAL | Denied | 1. Must submit as builds. 2. Must fix alarm issues with how the duct detectors are reporting to the proprietary monitor at TMC. Half reported as alarm and half as trouble. Should be supervisory. 3. Also, the pull station sounded a local alarm that reported to the panel on site, but was not received at TMC's panel. What Passed - All duct detectors were set off by smoke. Both the Lobby Main and the IOP entrance doors auto unlocked when the pull station was pulled. |
|
06/01/2015 | FIRE - ALARM FINAL | Denied | 1. Tested 4 air handlers duct detectors failed to stay in the latch position. All air handlers to be set as latch and stay latched until reset is done at the FACP. All 4 air handlers started automatically without the reset. 2. Need to clear DACT #1 and #2 troubles on panel 3. Need to clear LCD 7100 #5 trouble from panel 4. Need to have a clear panel before final will be given 5. Need as bults for the following: labeling changes, pull stations remove, annunciator panel's new locations, strobe removed. 6. Corridor #130 horn/strobes are not synchronized. |
|
05/28/2015 | FIRE - ALARM FINAL | Cancelled |