Permit: T15BU00072

Parcel: 124051160


Addresses:

746 E 5TH ST

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
02/23/2015 FIRE - ALARM FINAL Approved
02/03/2015 FIRE - ALARM FINAL Not ready for Inspection
02/02/2015 FIRE - ALARM FINAL Partial Approval 1. Need a lock out on the #6 breaker
2. Sign the laundry room door and the fire alarm room with "FACP"
3. Install lights inside the fire alarm room
4. Need a F.D. key box installed on main gate with the following keys insode it:
a. Main get key
b. Laundry room door key
c. Fire alarm room key
d. Fire alarm box FACP
Note: each key shall be label with a brass tag stating what the key is used for.