Inspection History Details
Inspection Status: Approved
Inspection History: OUTDOOR LIGHTING FINAL
Permit Number - T14OT01570
Inspection Description - OUTDOOR LIGHTING FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/16/2015 | OUTDOOR LIGHTING FINAL | Approved | APPROVED PER KEN V. | |
12/31/2014 | OUTDOOR LIGHTING FINAL | Correction Required | T14OT01570 Exposed lamp sign fixtures shall conform to the City of Tucson Outdoor Lighting Code (Ord #10963) as listed at section 501.4. Compare total outdoor fixture output to the budget based on property size and zone location (Table 401.1). Include all existing and proposed fixtures in the calculation. The rated color temperature of proposed fixtures shall not exceed 3500K, Section 402 and intensity of 200 nits, Section 501.5. Notate the plans, or provide manufacturer spec sheet with color temperature rating. Provide a control schedule in conformance with Table 501.5 limiting hours of illumination. The curfew time is 12:00 A.M. unless business activities continue after this time. Notate the closing time. The 2012 Outdoor Lighting Code may be found on The City of Tucson Website under: www.tucsonaz.gov/pdsd; Codes, Standards, Ordinances & Guidelines; Building Codes. Ken Van Karsen Electrical Plan Review PDSD, City of Tucson 520-837-4906 Kenneth.VanKarsen@tucsonaz.gov |