Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 06/28/2015 |
SIGN ELECTRIC |
|
Approved |
|
| 06/17/2015 |
SIGN ELECTRIC |
|
Cancelled |
|
| 06/01/2015 |
SIGN ELECTRIC |
|
Not ready for Inspection |
THE SIGN INSTALLER FOR COOK AND COMPANY OPENED THE SIGNS RACEWAY FOR THIS INSPECTION. THE RACEWAY IS INCOMPLETE AND WILL NEED TO BE CHANGED PRIOR TO SCHEULING THE FINAL INSPECTION. THE RACEWAY IS A THREE SIDED RACEWAY, IT IS ATTACHED TO THE VERTICAL SUPPORTS OF THE SIGN AND DOESN NOT HAVE A BACK PANEL THAT MAKES THE RACEWAY FULLY ENCLOSED. REACHING UNDERNEATH THE RACEWAY AND AROUND THE ENCLOSURE YOU ARE ABLE TO GRAB THE WIRES. PER THE SPECIFICATIONS IN THE 2011 NATIONAL ELECTRIC CODE SECTION 600.8 "ENCLOSURES" LIVE PARTS ARE TO BE ENCLOSED. I WILL VERIFY THIS INFORMATION WITH DAN SANTA CRUZ PRIOR TO ADVISING THE CONTRACTOR OF THE NECESSARY REPAIRS THAT ARE NEEDED. |
| 05/29/2015 |
SIGN ELECTRIC |
|
Not ready for Inspection |
TALKED WITH PERSONNEL INSIDE THE SITE TOO VERIFY THE INTERNAL ASPECTS OF THIS SIGN. |