Permit: T14OT00779

Parcel: 11618348C

Inspection Status: Approved

Inspection History: SIGN SITE REVIEW

Permit Number - T14OT00779

Inspection Description - SIGN SITE REVIEW

Inspection Status - Approved

Date Description Inspector Results Comments
07/10/2014 SIGN SITE REVIEW Approved CONTRACTOR BROUGHT IN REVISED PLANS. CHECK VALUATION (APPEARS INCORRECT AMOUNT ENTERED, SIMILAR PROJECT WITH SIGN HALF THE SIZE HAD SAME VALUATION AS NOTED ON THIS APPLICATION) ADD HEIGHT TO TOP OF SIGN ON DRAWING TO MATCH REVISED APPLICATION, THIS CAN BE DONE IN PERSON AT PERMIT PICK UP.
06/30/2014 SIGN SITE REVIEW Correction Required PERMIT T14OT00779
REMOVE EXIST SIGN/INSTALL (1) ILLUM WALL SIGN
AT: H & R BLOCK, 1317 W SAINT MARY'S RD
REVIEWER: HEATHER.THRALL@TUCSONAZ.GOV


THE FOLLOWING CODES APPLY TO THIS REVIEW: OUTDOOR LIGHTING CODE (OLC), UNIFIED DEVELOPMENT CODE (UDC), INTERNATIONAL BUILDING CODE (IBC), SIGN CODE (SC), NATIONAL ELECTRIC CODE (NEC)

1) P.D.S.D. SCANNING POLICY - PLEASE ENLARGE ALL PRINT ON PLANS TO MINIMUM OF 12 POINT, NO DIMENSIONS ON THE DRAWINGS ARE LEGIBLE - INFO REQUIRED FOR REVIEW, INSPECTIONS & RECORDS.

2) PER GENERAL BUSINESS DISTRICT S.C. 3-77, FRONTAGE LISTED ON APPLICATION AT 61.75 LINEAR FEET DOES NOT MATCH RECORD ON FILE FOR THIS SUITE AT 39.5 LINEAR FEET. (ACKNOWLEDGED SIGN AREA PROPOSED AT 90.5 SQFT IS WITHIN CODE). REVISE FRONTAGE ON APPLICATION. CORRECT THROUGHOUT PACKET AS APPLIES.

3) PER S.C. 3-18, LIST TYPE/SIZE/TYPICAL NUMBER OF FASTENERS AND NOTE TYPE OF WALL SIGN TO BE MOUNTED TO.

4) PER S.C. 3-18 - LIST NUMBER OF VOLTS, AMPS, CIRCUITS. (ACKNOWLEDGED L.E.D. LIGHT SOURCE LISTED AND SHUT OFF SWITCH AND TIMER LISTED, THANK YOU.)

5). PER SC 3-18, 3-32, 3-77 - SHOW FRONTAGE DIMENSION BOTH ON APPLICATION AND ON PROPOSED SIGN INSTALL ELEVATION.

EMAIL REVISED SHEETS TO DSD_SIGNS@TUCSONAZ.GOV AND LIST SIGN PERMIT NUMBER AND BUSINESS NAME IN SUBJECT HEADING.
06/20/2014 SIGN SITE REVIEW Correction Required The electrical detail submitted with permit is unreadable. Resubmit detail on a separate sheet

Include the following on detail:

1) SHOW DISCONNECT/ SERVICE SWITCH PER N.E.C. ARTICLE 600.

2) SHOW OR NOTE 7 DAY PROGRAMMABLE TIMER TO COMPLY WITH OUTDOOR LIGHTING CODE.