Permit: T14OT00273

Parcel: 117067140

Inspection Status: Approved

Inspection History: SIGN SITE REVIEW

Permit Number - T14OT00273

Inspection Description - SIGN SITE REVIEW

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2014 SIGN SITE REVIEW Approved CONTRACTOR PROVIDED REVISED PLANS.
03/25/2014 SIGN SITE REVIEW Partial Approval PERMIT T14OT00273
FOR: NEW WALL & PROJECTING SIGN
AT: 345 E CONGRESS ST., #101
REVIEWER: H.THRALL (HEATHER.THRALL@TUCSONAZ.GOV)

2nd REVIEW: 3/25/14 (Resubmitted drawings)

THE FOLLOWING CODES APPLY: NATIONAL ELECTRICAL CODE (NEC), INTERNATIONAL BUILDING CODE (IBC), CHAPTER 3 OF THE TUCSON CODE - SIGN CODE (SC), & CH, 4 & 5 OUTDOOR LIGHTING CODE (OLC).


FOR ALL SIGNS/ALL DRAWINGS:

1) ON ALL DRAWINGS: FOR RECORDS SCANNING, INCREASE FONT TO 12 POINT MINIMUM. (Acknowledged corrections, however on sheet 2 of 4 an area to enlarge type was missed - see attachment detail for projecting sign, enlarge all font in this detail to 12 point)

PROJECTING SIGNAGE:

2) PER SC SEC. 3-82.D.7:C. MAXIMUM HEIGHT 12' PROJECTING SIGN. PROPOSAL EXCEEDS THAT, REVISE ON BOTH SHEETS 3 & 4. (Acknowledged sheet 3 is now corrected to show sign is now a max of 12' to top from pedestrian surface below, but sheet 4 is missing and is needed.)

PLEASE EMAIL CORRECTED SHEETS TO HEATHER.THRALL@TUCSONAZ.GOV
03/19/2014 SIGN SITE REVIEW Correction Required PERMIT T14OT00273
FOR: NEW WALL & PROJECTING SIGN
AT: 345 E CONGRESS ST., #101
REVIEWER: H.THRALL (HEATHER.THRALL@TUCSONAZ.GOV) 3/18/2014

THE FOLLOWING CODES APPLY: NATIONAL ELECTRICAL CODE (NEC), INTERNATIONAL BUILDING CODE (IBC), CHAPTER 3 OF THE TUCSON CODE - SIGN CODE (SC), & CH, 4 & 5 OUTDOOR LIGHTING CODE (OLC).


FOR ALL SIGNS/ALL DRAWINGS:

1) ON ELECTRICAL DIAGRAMS: PER O.L.C. CH 4, SEC 403.5.1 The means of controlling the specific "off" curfew shall be by a 24 hour timing device that includes stand-by power to maintain the time and program for a minimum of 6 hours. SHOW TIMER OR NOTE ONE TO BE PROVIDED.

2) ON ALL DRAWINGS: FOR RECORDS SCANNING, INCREASE FONT TO 12 POINT MINIMUM.

3) WALL SIGN ATTACHMENT DETAIL SHOWS "STEEL STUD FRAMED WALL" BUT ELEVATION DRAWING APPEARS TO SHOW BLOCK WALL. PROJECTING SIGN DETAIL LISTS "STEEL STUD FRAME WALL" BUT 2ND DIAGRAM BELOW LISTS BLOCK WALL. CLARIFY WHICH IS WALL TYPES APPLY & REVISE DETAILS AS NECESSARY. CHECK ATTACHMENT METHOD IS SUFFICIENT FOR TYPE OF WALL.

WALL SIGNAGE:

4) PER NEC.600 - CLARIFY NUMBER OF CIRCUITS.

PROJECTING SIGNAGE:

5) A review of approved development plan, DP12-0029, shows the proposed projecting sign - as submitted on a location map - is to extend over land currently owned by the City of Tucson as a common area. A re-plat is underway to convey the common area to a private H.O.A. with easements conveyed for public accessed sidewalks. Given the re-plat, the City of Tucson Real Estate and Parkwise Divisions have no objection to the proposed placement of the projecting sign over (aerially) the currently city owned land.
A) As HOA is not in place yet, Per SC 3-18, provide letter of permission from developer/owner- Jim Campbell - allowing sign placement.

B) For records of where the property line is (street curb) in relation to projecting sign (as property line is not on submitted location map), show the proposed signage on a copy of the approved DP12-0029 site plan sheet.

6) PER SC SEC. 3-82.D.7:C. MAXIMUM HEIGHT 12' PROJECTING SIGN. PROPOSAL EXCEEDS THAT, REVISE ON BOTH SHEETS 3 & 4.

7) PER SC SEC. 3-82.D.7.E. MAXIMUM PROJECTION 5' FROM BUILDING WALL. PROPOSAL DOES NOT SHOW THIS INFORMATION, ONLY SHOWS CABINET DIMENSIONS. PROVIDE TOTAL PROJECTION FROM WALL.

**** DEPENDING UPON RESPONSES PROVIDED IN THE RESUBMITTAL, FURTHER REVIEW COMMENTS MAY BE FORTHCOMING****