Permit: T14OT00184

Parcel: 141176810


Addresses:

7431 S HOUGHTON RD


Inspection Status: Approved

Inspection History: SIGN EXCAVATION

Permit Number - T14OT00184

Inspection Description - SIGN EXCAVATION

Inspection Status - Approved

Date Description Inspector Results Comments
09/25/2014 SIGN EXCAVATION Approved FOOTING EXCAVATION IS 7' DEEP AND THE CENTER IS 53'+/-6" FROM THE FOC.
09/22/2014 SIGN EXCAVATION Denied PLACE SIGN AT 71 FEET FROM ROW AS SHOWN ON PERMIT OR CHANGE PERMIT TO SHOW WHERE EXCAVATION IS AS THE REQUIRED SETBACK.
09/09/2014 SIGN EXCAVATION Denied DEPTH @ 6' 6", PLAN SHOWS 7'
SETBACK IS 55', PERMIT SHOWS 71.5'

DENIED, CALL FOR RE-INSPECTION
07/28/2014 SIGN EXCAVATION Denied LOOKED AT THE SITE ONCE AGAIN TO VERIFY THE PROPERTY LINE LOCATION TO ENSURE THAT THE SIGN IN WITHIN THE PROPERTY BOUNDARIES. IT APPEARS THAT THE FOUNDATION IS PARTIALLY LOCATED IN THE COMMON AREA FOR THE SUBDIVISION AND WILL NEED TO BE MOVED 15 INCHES TO THE SOUTH. I SHOWED HEATHER THE PHOTOS AND DISCUSSED THIS WITH HER. SHE WILL CONTACT THE SIGN CONTRACTOR AND ADVISE THEM OF THE ISSUES THAT STILL REMAIN.
06/25/2014 SIGN EXCAVATION Denied SIGN SETBACK INSUFFICIENT, 71.5 FEET FROM CENTER OF HOLE TO HOUGHTON FACE OF CURB.

PROPERTY LINE IS NOT MARKED - SIGN MUST BE 7.5' SETBACK FROM PROPETY LINE/START OF SCENIC BUFFER.

IN ADDITION, THE DEPTH OF THE FOOTER IS INSUFFICIENT PER THE APPROVED PLANS SHOULD BE 7 FEET DEEP IS ONLY 6.5 DEEP