Inspection History Details
Inspection Status: Approved
Inspection History: SIGN EXCAVATION
Permit Number - T14OT00184
Inspection Description - SIGN EXCAVATION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/25/2014 | SIGN EXCAVATION | Approved | FOOTING EXCAVATION IS 7' DEEP AND THE CENTER IS 53'+/-6" FROM THE FOC. | |
09/22/2014 | SIGN EXCAVATION | Denied | PLACE SIGN AT 71 FEET FROM ROW AS SHOWN ON PERMIT OR CHANGE PERMIT TO SHOW WHERE EXCAVATION IS AS THE REQUIRED SETBACK. | |
09/09/2014 | SIGN EXCAVATION | Denied | DEPTH @ 6' 6", PLAN SHOWS 7' SETBACK IS 55', PERMIT SHOWS 71.5' DENIED, CALL FOR RE-INSPECTION |
|
07/28/2014 | SIGN EXCAVATION | Denied | LOOKED AT THE SITE ONCE AGAIN TO VERIFY THE PROPERTY LINE LOCATION TO ENSURE THAT THE SIGN IN WITHIN THE PROPERTY BOUNDARIES. IT APPEARS THAT THE FOUNDATION IS PARTIALLY LOCATED IN THE COMMON AREA FOR THE SUBDIVISION AND WILL NEED TO BE MOVED 15 INCHES TO THE SOUTH. I SHOWED HEATHER THE PHOTOS AND DISCUSSED THIS WITH HER. SHE WILL CONTACT THE SIGN CONTRACTOR AND ADVISE THEM OF THE ISSUES THAT STILL REMAIN. | |
06/25/2014 | SIGN EXCAVATION | Denied | SIGN SETBACK INSUFFICIENT, 71.5 FEET FROM CENTER OF HOLE TO HOUGHTON FACE OF CURB. PROPERTY LINE IS NOT MARKED - SIGN MUST BE 7.5' SETBACK FROM PROPETY LINE/START OF SCENIC BUFFER. IN ADDITION, THE DEPTH OF THE FOOTER IS INSUFFICIENT PER THE APPROVED PLANS SHOULD BE 7 FEET DEEP IS ONLY 6.5 DEEP |