Permit: T14MH00033

Parcel: 138112110


Addresses:

266 E VALESKA RD

Inspection Status: Not Applicable

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
09/24/2014 ELECTRIC - RECONNECT Not Applicable IVRS - Inspection :*
09/23/2014 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
09/23/2014 ELECTRIC - RECONNECT Not ready for Inspection ITEMS 2,5,8 STILL NOT CORRECTED ANY FURTHER FAILED INSPECTION WILL RESULT IN A RE-FEE
09/17/2014 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/17/2014 ELECTRIC - RECONNECT Denied 1.THIS IS NOT A RECONNECT, THIS IS A NEW SERVICE WITH SERVICE ENTRANCE ON A PLE
2.VERIFY DEPTH OF POLE (MINIMUM 5)
3.VERIFY (EXPOSE) UNDERGROUND CONDUIT DEPTH
4.PROVIDE 2 GROUND RODS MINIMUM DEPTH 6
5.PROVIDE BONDING OF GAS AND WATER LINES
6.PERMIT TO BE REVISED
7.METER BOARD TO BE TREATED FOR OUTDOOR USE
8.2 HOLE PIPE STRAPS REQUIRED FOR RISER SUPPORT