Permit: T14ME00033

Parcel: 113091910


Addresses:

926 E ALTURAS ST


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T14ME00033

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/14/2014 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
05/12/2014 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/12/2014 MECHANICAL - INTERMEDIATE Denied 1. CONDUIT NOT PROPERLY SUPPORTED AT SERVICE PANEL
2. THIS IS A NEW INSTALLATION, NOT REPLACEMENT. PROVIDE GAS PERMIT, ELEC PERMIT, & STRUCTURAL LOAD CALCS
3. ALL ROOF TO DUCT WORK TO HAVE 2" (R-8) INSULATION
4. ELEC NOT WIRED TO CODE
5. PVC SUPPORT NOT TO EXCEED 48"
6. PVC TO BE PROPERLY COATED FOR UV PROTECTION
7. CONDENSATE NOT PROPERLY TERMINATED
8. DUCT NOT PROPERLY SEALED
9. TURNING VANES OR RADIUS TEE REQUIRED AT CHANGE OF DIRECTION