Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2015 | ELECTRIC - FINAL | Approved | ||
| 06/17/2015 | ELECTRIC - FINAL | Denied | 1 LABELING NOT DISTINGWISHABLE FROM ONE ANOTHER 408.4 2 LOCKOUT INSTALLED BACKWARDS 3 COLOR CODE FOR WIRES 277V COLORS BEING USED-THIS IS COMMERCIAL 4 INSTALL ALL STRANDS UNDER TERMINAL LUGS 5 BOND JUNCTION BOX ENCLOSURES 6. FILL UNUSED OPENINGS |
|
| 11/07/2014 | ELECTRIC - FINAL | Partial Approval | 1. RECALL FOR LOAD SIDE SERVICE OK GROUNDING |