Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2014 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/23/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/23/2014 | ELECTRIC - FINAL | Denied | - PROVIDE PAST INSPECTION COPY - VERIFY WATER & GAS BONDING - #8 CU WIRE SHOULD BE ON 50 AMP CIRCUIT BREAKER NOT 60 AMP - GROUND 6X6 J-BOX USING APPROVED LUG - UNISTRUT NOT SECURED TO WALL OF STRUCTURE - DOOR (COVER) TO SERVICE PANEL NOT CLOSING PROPERLY - 2 HOLE STRAPS FOR RISER CONDUIT NOT SCREWED DOWN |
|
| 04/22/2014 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |