Permit: T14EL00040

Parcel: 130070150


Addresses:

3720 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/24/2014 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/23/2014 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/23/2014 ELECTRIC - FINAL Denied - PROVIDE PAST INSPECTION COPY
- VERIFY WATER & GAS BONDING
- #8 CU WIRE SHOULD BE ON 50 AMP CIRCUIT BREAKER NOT 60 AMP
- GROUND 6X6 J-BOX USING APPROVED LUG
- UNISTRUT NOT SECURED TO WALL OF STRUCTURE
- DOOR (COVER) TO SERVICE PANEL NOT CLOSING PROPERLY
- 2 HOLE STRAPS FOR RISER CONDUIT NOT SCREWED DOWN
04/22/2014 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*