Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T14DV09967
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2014 | INSP - INITIAL CODE ENFORCMENT | Approved | EMERGENCY CALL OUT BY TFD THE WOMEN'S SAUNA ROOM SPRINKLER HEAD DID DISCHARGE AND FLOOD THE COMPARTMENT. THE ALARM DID NOT FUNCTION ACCORDING TO TFD. THE SAUNA SPRINKLER HEAD IS RATED AT 200DEGREES. THE SAUNA IS MAXIMUM TEMPERATURE IS SET AT 160 DEGREES. HISTORY: ON NOVEMBER 17, 2014. THEY HAD THE SAME EXACT ISSUE. THE SPRINKLER HEAD WAS REPLACED WITH A 200 DEGREE HEAD. SABINO ELECTRIC WAS THE COMPANY ON SITE. AFTER SPEAKING TO TFD, I QUESTIONED REASONS WHY THE HEAD DISCHARGED AND THERE WAS NO FIRE. I ASKED ABOUT THE AGE OF THE SAUNA AND IS THE THERMOSTAT READING IS THE READING INSIDE ACCURATE WITH THE EXTERNAL CONTROL? THE ALARM SYSTEM DID NOT SOUND? THE POWER WAS SHUT OFF TO THE SAUNA UNIT AND THE TIMER. THE SPRINKLER SYSTEM WAS SHUT DOWN TO THE BUILDING BY TFD, SO I ISSUED A NOTICE AND ORDER TO CONDEMN THE BUILDING. A PERMIT MAY BE REQUIRED DEPENDING ON THE ELECTRIC INSPECTION ON THE SAUNA AND CONTROLS.. THE BUILDING MAY RE OPEN IF ALL THE REQUIREMENTS OF THE FIRE DEPT ARE MET. AT THIS TIME CURRENTLY WORKING WITH THE FIRE INSPECTOR.. |