Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2014 | INSP - INITIAL CODE ENFORCMENT | Approved | VISITED SITE, MET WITH TFD CHIEF ROB RODRIQUEZ WHO ALLOWED ENTRY INTO UNIT 1427. I FOUND THE CEILING LIGHT/FAN HANGING AND THE WIRING TO THE FAN PULLED DOWN THRU THE OPENING INTHE CEILEING WHERE PLASTER AND LATH HAD BEEN REMOVED. FROM THE LARGE OPENING I ALSO FOUND ELECTRICAL FEEDS TO THE INTERIOR SUBPANEL FED OVER THE PARTING WALL. ALL WIRING FROM MAIN SERVICE PANEL TO THE SUBPANELS RAN THRU THE FIRE DAMAGED UNIT 1429. TEP ALSO HAD ACCESS TO THE UNIT AND LOCKED THE PANEL OUT. DUE TO THE EXPOSED WIRING IN THE UNIT AND THE POSSIBLE FIRE DAMAGED FEEDS TO THE SUB PANEL IT WAS DECIDED TO KEEP THE POWER OFF. OCCUPANTS FOUND HOUSING WITH OTHER STUDENTS WITHIN THE COMPLEX. MANAGER YISHI GARRARD HAD NO PROBLEM WITH THE HOUSING SITUATION, STATED ALL OCCUPANTS WERE BUSINESS STUDENTS AND A CLOSE GROUP. > LARGE HOLE LEFT IN PLASTER CEILING AND LATH DUE TO FIRE NEXT DOOR. > EXPOSED WIRING TO THE LIGHT/FAN FROM THE SWITCH. WIRE HANGING BELOW THE LIGHT FIXTURE, EXPOSED WIRING FROM MAIN SERVICE PANEL TO THE SUB PANEL ALSO LEFT EXPOSED. > POWER TURNED OFF BY TFD AND PANEL LOCKED OUT BY TEP. > SOUTH WEST GAS FOUND MINOR GAS LEAK TO THE HEATING / COOLING UNIT. OCCUPANTS DID FIND HOUSING. YISHI GARRARD DID SIGN FOR ALL DOCUMENTS AND DID NOTIFIED OWNER DAN JAMES. STRUCTURE PROPERLY SECURED BY YISHI GARRARD. |