Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/14/2014 |
INSP - FOLLOW UP CODE ENFORCE |
|
Approved |
Abated Close Case. |
| 11/03/2014 |
INSP - FOLLOW UP CODE ENFORCE |
|
Approved |
Electrical items have been abated. I sent LeeRay Hanley an email to close the expired permit for this activity. The yard is almost finished. I will return next week. |
| 10/29/2014 |
INSP - FOLLOW UP CODE ENFORCE |
|
Approved |
Meet with the owner and electrical contractor on site. The contractor will fix the problems and I will check on Monday. |
| 10/22/2014 |
INSP - FOLLOW UP CODE ENFORCE |
|
Approved |
Visited the site and was able to review the service upgrade. The neutral and ground conductors were split between termanal lugs which is not allowed by NEC code. The grounding Electrode Conductor was cut and missing. All other items were OK. |
| 10/17/2014 |
INSP - FOLLOW UP CODE ENFORCE |
|
Approved |
Visited site progress is being made extend 10 days. |