Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T14DV00969
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/10/2014 | INSP - INITIAL CODE ENFORCMENT | Approved | I STARTED INSPECTING THE PARK ON 2-10-2014 AND FINISHED THE LAST UNIT ON 2-18-2014, BELOW ARE THE VIOLATIONS THIS PARK HAS 5 MAIN SERVICE DISCONNECTS LOCATED IN FIVE DIFFERENT LOCATIONS IN THE PARK. THERE IS NO LABELING SO I WILL LIST THEM FROM WEST TO EAST AND GIVE SPACE NUMBERS ACCORDING TO THERE LOCATION. THE FIRST SERVICE DISCONNECT LOCATION IS LOCATED AT THE REAR OF UNIT 4. THE MAKE UP IS TWO 200 AMP SERVICE DISCONNECTS. THE VIOLATIONS ARE AS FOLLOWS; NO LABELING, THE GROUNDING ELECTRODE CONDUCTOR AS A SPICE WITH AN IMPROPER CONNECTOR, UNUSED OPENINGS, NO ACCESS TO SERVICE DISCONNECTS, CLEARANCE ISSUES. A PERMIT IS REQUIRED FOR THE REPAIRS THE SECOND SERVICE DISCONNECT LOCATION IS LOCATED ON THE SOUTH WALL OF THE HOUSE MARKED AS UNIT 21. THE MAKE UP IS TWO 200 AMP SERVICE DISCONNECTS AND A 60 AMP DISCONNECT FOR THE HOUSE. BELOW ARE THE VIOLATIONS. THE GUTTER BOX'S GROUNDING ELECTRODE CONDUCTOR HAS BEEN CUT, LATER WAS REPAIRED WITHOUT A PERMIT. THE GUTTER BOX ALSO HAS ARCING SIGNS UNDERNEATH AN OPENING AND LATER WAS COVERED. THE 100 AMP MAIN DISCONNECT IS NEW AND WAS INSTALLED WITH OUT A PERMIT. THE DISCONNECT HAS TWO FEEDERS WITH CUT PIECES STRAND WIRES TO EACH LUG TO ALLOW FOR THE MULTIPLE FEEDERS. THERE ARE MULTIPLE FEEDERS ON EACH LUG. THE METAL CONDUIT IS NOT CONTINUOUS AS IT ENTERS THE MAIN DISCONNECT TOP AND BOTTOM. NO LABELING. THE SECOND 100 AMP MAIN DISCONNECT HAS UNUSED OPENINGS AND THE CONDUIT IS NOT CONTINUOUS AS IT ENTERS THE MAIN DISCONNECT. NO LABELING. THE BACKER BOARD TO THE ENTIRE ELECTRICAL SYSTEM IS DETERIORATED AND MUST BE REPLACED IN THE CONFIGURATION THERE IS 60 AMP PANEL WHICH IS THE DISCONNECT FOR THE SMALL HOUSE. THIS SYSTEM HAS A CORD BETWEEN THE METER AND THE ADJACENT MAIN DISCONNECT THE CORD IS BEING USED AS PERMANENT WIRING. THE CORD IS BEING ENERGIZED FROM AN ILLEGAL MULTIPLE LUG IN THE MAIN DISCONNECT. THIS PANEL HAS A BACK FEED BREAKER WHICH DOESN'T HAVE THE HOLD DOWN. THE GROUND AND NEUTRALS ARE NOT SEPARATED. THE DEAD FRONT IS NOT SECURED. NO LABELED A PERMIT IS REQUIRED FOR THE REPAIRS TO ALL THE EQUIPMENT. THE THIRD SERVICE DISCONNECT LOCATION IS NORTH OF THE HOUSE MARKED AS UNIT 30, THE MAKE UP IS ONE 200 AMP SERVICE DISCONNECT. THIS 200 AMP SERVICE DISCONNECT PROVIDES SERVICE TO UNITS 23, 25, 26, 28, 29, 30. THE VIOLATIONS ARE AS FOLLOWS; DEAD FRONT NOT SECURED, USED OPENING, NO ACCESS TO SERVICE DISCONNECT. A PERMIT IS REQUIRED FOR UNDERGROUND WORK, NEW CONDUIT AND POSSIBLE NEW FEEDERS. THIS WORK WAS IN 12/2013 THE FOURTH SERVICE DISCONNECT LOCATION IS LOCATED AT THE REAR OF THE LAUNDRY ROOM. THE MAKE UP IS 4 / 200 AMP SERVICE DISCONNECTS AND ONE 100 AMP DISCONNECT FOR THE LAUNDRY ROOM. THE VIOLATIONS ARE AS FOLLOWS; THE LAUNDRY ROOM MAIN DISCONNECT HAS NO LABELING. THE INTERIOR LAUNDRY ROOM HAS NO LIGHTING AND ABANDON CONDUIT WITH EXPOSED WIRING. THE FIFTH SERVICE DISCONNECT LOCATION IS AT THE REAR OF UNIT 57. THE MAKE UP IS TWO 200 AMP SERVICE DISCONNECTS. THE VIOLATIONS ARE AS FOLLOWS: NO ACCESS TO SERVICE DISCONNECTS, USED OPENINGS, NO LABELING. ELECTRICAL VIOLATIONS BELOW ARE THE PEDESTAL / DISCONNECTING MEANS VIOLATIONS UNIT 1 PEDESTAL UNUSED OPENINGS NO LABELING UNIT 2 PEDESTAL OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION) UNUSED OPENINGS NO LABELING UNIT 3 PEDESTAL OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION) NO LABELING UNIT 4 PEDESTAL OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION) NO LABELING UNIT 5 PEDESTAL UNUSED OPENINGS THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS NO LABELING UNIT 6 PEDESTAL NO LABELING UNIT 7 PEDESTAL UNUSED OPENINGS UNABLE TO DETERMINE BREAKER AMPACITY NO LABELING UNIT 8 PEDESTAL THE MAIN BREAKER IS 100 AMPS, THE POWER SUPPLY CORD IS RATED FOR 50 AMPS. THE BREAKER IS NOT PROPERLY SEATED UNUSED OPENINGS NO LABELING UNIT 9 PEDESTAL UNUSED OPENINGS NO LABELING UNIT 10 PEDESTAL UNUSED OPENINGS THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS NO LABELING UNIT 11 PEDESTAL NO LABELING UNIT 12 PEDESTAL OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION) UNUSED OPENINGS THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS NO LABELING UNIT 13 PEDESTAL OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION) UNUSED OPENINGS NO LABELING THE MAIN BREAKER CONSIST OF TWO 30 AMP SINGLE POLE TYPE BREAKERS WITH NO HANDLE TIE UNIT 14 PEDESTAL OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION) THE MAIN BREAKER IS 50 AMPS, THE POWER SUPPLY CORD IS RATED FOR 30 AMPS NO LABELING UNIT 16 PEDESTAL NO LABELING THE POWER SUPPLY CORD HAS MISSING INSULATION AND THE CONDUCTORS HAVE TAPE AT THE ENDS. UNIT 17 PEDESTAL UNUSED OPENINGS THE POWER SUPPLY CORD HAS MISSING INSULATION AND THE CONDUCTORS HAVE TAPE AT THE ENDS. NO LABELING UNIT 18 PEDESTAL THE RECEPTACLE TO THE MAIN BREAKER IS NOT PROPERLY SEATED. NO LABELING UNIT 19 PEDESTAL UNUSED OPENINGS THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS NO LABELING UNIT 20 PEDESTAL UNUSED OPENINGS UNABLE TO DETERMINE BREAKER AMPACITY NO LABELING UNIT 22 PEDESTAL THE MAIN BREAKER IS 50 AMPS, THE POWER SUPPLY CORD IS RATED FOR 30 AMPS UNUSED OPENINGS NO LABELING UNIT 23 PEDESTAL NO LABELING UNIT 24 PEDESTAL NO LABELING UNUSED OPENINGS UNIT 25 PEDESTAL NO LABELING UNUSED OPENINGS UNIT 26 PEDESTAL NO LABELING UNIT 27 PEDESTAL NO LABELING MISSING DEAD FRONT UNIT 28 PEDESTAL EXPOSED CONDUCTORS MISSING PEDESTAL LOWER COVER NO LABELING UNIT 29 PEDESTAL NO LABELING MISSING DEAD FRONT UNIT 30 (HOUSE) NO LABELING UNIT 32 PEDESTAL NO LABELING UNUSED OPENINGS CLEARANCE IS OBSTRUCTED BY SEWER PIPE (WITHIN THE 36 INCHES) UNIT 33 PEDESTAL NO LABELING UNUSED OPENINGS UNAPPROVED POWER SUPPLY CORD (UF CABLE BEING USED AS POWER SUPPLY CORD) PEDESTAL IS NOT PROPERLY SUPPORT PEDESTAL HAS MISSING HARDWARE THE MAIN BREAKER CONSIST OF TWO 20 AMP SINGLE POLE TYPE BREAKERS WITH NO HANDLE TIE UNIT 34 PEDESTAL NO LABELING UNUSED OPENINGS OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION) PEDESTAL HE MISSING HARDWARE UNIT 35 PEDESTAL NO LABELING UNIT 36 PEDESTAL OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION) NO LABELING UNUSED OPENINGS CLEARANCE IS OBSTRUCTED BY FENCE AND MATERIAL NON METALLIC SHEATHED CABLE IS BEING USED AS A SUPPLY CORD. THERE IS BROKEN A RECEPTACLE THE RECEPTACLE BEING USED IS IMPROPER. UNIT 37 PEDESTAL NO LABELING UNIT 38 PEDESTAL NO LABELING CLEARANCE IS OBSTRUCTED BY HOSE AND MISCELLANEOUS EQUIPMENT UNIT 39 PEDESTAL NO LABELING UNIT 40 PEDESTAL NO LABELING UNUSED OPENINGS THE MAIN BREAKER IS 60 AMPS, THE POWER SUPPLY CORD IS RATED FOR 50 AMPS UNIT 41 PEDESTAL NO LABELING UNUSED OPENINGS UNIT 42 PEDESTAL NO LABELING UNUSED OPENINGS PEDESTAL HAS MISSING HARDWARE UNABLE TO DETERMINE BREAKER AMPACITY UNIT 43 PEDESTAL NO LABELING UNUSED OPENINGS PEDESTAL HAS MISSING HARDWARE THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS UNIT 44 PEDESTAL NO LABELING EXTENSION CORDS ARE BEING USED EMPLACE OF A POWER SUPPLY CORD UNIT 45 PEDESTAL NO LABELING UNUSED OPENINGS UNAPPROVED POWER SUPPLY CORD (UNPROTECTED CABLE BEING USED AS POWER SUPPLY CORD) UNIT 46 PEDESTAL MISSING PEDESTAL HARDWARE NO DEAD FRONT NO LABELING UNUSED OPENINGS UNIT 47 PEDESTAL NO LABELING UNIT 48 PEDESTAL NO LABELING UNUSED OPENINGS THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS UNIT 49 PEDESTAL NO LABELING UNUSED OPENINGS THE MAIN BREAKER IS 100 AMPS, THE POWER SUPPLY CORD IS RATED FOR 50 AMPS UNIT 50 PEDESTAL NO LABELING UNIT 51 PEDESTAL NO LABELING CLEARANCE IS OBSTRUCTED BY FENCE. OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION) UNIT 52 PEDESTAL OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION) NO LABELING NO DEAD FRONT UNUSED OPENINGS UNIT 53 PEDESTAL NO LABELING PEDESTAL HE MISSING HARDWARE UNIT 54 PEDESTAL CLEARANCE IS OBSTRUCTED BY FENCE UNUSED OPENINGS NO LABELING POWER SUPPLY CORD IS CONNECT DIRECT TO THE METER ( NO OVER CURRENT PROTECTION) UNIT 55 PEDESTAL THE MAIN BREAKER IS 50 AMPS, THE POWER SUPPLY CORD IS RATED FOR 40 AMPS UNUSED OPENINGS NO LABELING FASTENERS ARE MISSING TO THE DUAL PEDESTAL HARDWARE. UNIT 56 PEDESTAL UNABLE TO DETERMINE BREAKER AMPACITY OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION) CLEARANCE IS OBSTRUCTED BY FENCE. PEDESTAL HAS MISSING HARDWARE UNUSED OPENINGS NO LABELING UNIT 57 PEDESTAL UNUSED OPENINGS NO LABELING THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS PVC CONDUIT IS NOT CONTINUOUS. UNIT 58 PEDESTAL NO LABELING UNIT 59 PEDESTAL CLEARANCE IS OBSTRUCTED BY FENCE. OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION) PEDESTAL BREAKER NOT PROPERLY SEATED (UNABLE TO SHUT OFF) UNIT 60 PEDESTAL NO LABELING OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION) |