Case: T14DV00969

Parcel: 14025101A


Addresses:

6001 S PARK AV


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T14DV00969

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
02/10/2014 INSP - INITIAL CODE ENFORCMENT Approved I STARTED INSPECTING THE PARK ON 2-10-2014 AND FINISHED THE LAST UNIT ON 2-18-2014, BELOW ARE THE VIOLATIONS
THIS PARK HAS 5 MAIN SERVICE DISCONNECTS LOCATED IN FIVE DIFFERENT LOCATIONS IN THE PARK. THERE IS NO LABELING SO I WILL LIST THEM FROM WEST TO EAST AND GIVE SPACE NUMBERS ACCORDING TO THERE LOCATION.

THE FIRST SERVICE DISCONNECT LOCATION IS LOCATED AT THE REAR OF UNIT 4. THE MAKE UP IS TWO 200 AMP SERVICE DISCONNECTS. THE VIOLATIONS ARE AS FOLLOWS; NO LABELING, THE GROUNDING ELECTRODE CONDUCTOR AS A SPICE WITH AN IMPROPER CONNECTOR, UNUSED OPENINGS, NO ACCESS TO SERVICE DISCONNECTS, CLEARANCE ISSUES. A PERMIT IS REQUIRED FOR THE REPAIRS

THE SECOND SERVICE DISCONNECT LOCATION IS LOCATED ON THE SOUTH WALL OF THE HOUSE MARKED AS UNIT 21. THE MAKE UP IS TWO 200 AMP SERVICE DISCONNECTS AND A 60 AMP DISCONNECT FOR THE HOUSE. BELOW ARE THE VIOLATIONS.
THE GUTTER BOX'S GROUNDING ELECTRODE CONDUCTOR HAS BEEN CUT, LATER WAS REPAIRED WITHOUT A PERMIT. THE GUTTER BOX ALSO HAS ARCING SIGNS UNDERNEATH AN OPENING AND LATER WAS COVERED.
THE 100 AMP MAIN DISCONNECT IS NEW AND WAS INSTALLED WITH OUT A PERMIT.
THE DISCONNECT HAS TWO FEEDERS WITH CUT PIECES STRAND WIRES TO EACH LUG TO ALLOW FOR THE MULTIPLE FEEDERS. THERE ARE MULTIPLE FEEDERS ON EACH LUG. THE METAL CONDUIT IS NOT CONTINUOUS AS IT ENTERS THE MAIN DISCONNECT TOP AND BOTTOM. NO LABELING.
THE SECOND 100 AMP MAIN DISCONNECT HAS
UNUSED OPENINGS AND THE CONDUIT IS NOT CONTINUOUS AS IT ENTERS THE MAIN DISCONNECT. NO LABELING.
THE BACKER BOARD TO THE ENTIRE ELECTRICAL SYSTEM IS DETERIORATED AND MUST BE REPLACED
IN THE CONFIGURATION THERE IS 60 AMP PANEL WHICH IS THE DISCONNECT FOR THE SMALL HOUSE.
THIS SYSTEM HAS A CORD BETWEEN THE METER AND THE ADJACENT MAIN DISCONNECT
THE CORD IS BEING USED AS PERMANENT WIRING. THE CORD IS BEING ENERGIZED FROM AN ILLEGAL MULTIPLE LUG IN THE MAIN DISCONNECT. THIS PANEL HAS A BACK FEED BREAKER WHICH DOESN'T HAVE THE HOLD DOWN. THE GROUND AND NEUTRALS ARE NOT SEPARATED. THE DEAD FRONT IS NOT SECURED.
NO LABELED
A PERMIT IS REQUIRED FOR THE REPAIRS TO ALL THE EQUIPMENT.

THE THIRD SERVICE DISCONNECT LOCATION IS NORTH OF THE HOUSE MARKED
AS UNIT 30, THE MAKE UP IS ONE 200 AMP SERVICE DISCONNECT. THIS 200 AMP SERVICE DISCONNECT PROVIDES SERVICE TO UNITS 23, 25, 26, 28, 29, 30.
THE VIOLATIONS ARE AS FOLLOWS; DEAD FRONT NOT SECURED, USED OPENING, NO ACCESS TO SERVICE DISCONNECT. A PERMIT IS REQUIRED FOR UNDERGROUND WORK, NEW CONDUIT AND POSSIBLE NEW FEEDERS. THIS WORK WAS IN 12/2013

THE FOURTH SERVICE DISCONNECT LOCATION IS LOCATED AT THE REAR OF THE LAUNDRY ROOM. THE MAKE UP IS 4 / 200 AMP SERVICE DISCONNECTS AND ONE 100 AMP DISCONNECT FOR THE LAUNDRY ROOM. THE VIOLATIONS ARE AS FOLLOWS;
THE LAUNDRY ROOM MAIN DISCONNECT HAS NO LABELING. THE INTERIOR LAUNDRY ROOM HAS NO LIGHTING AND ABANDON CONDUIT WITH EXPOSED WIRING.



THE FIFTH SERVICE DISCONNECT LOCATION IS AT THE REAR OF UNIT 57. THE MAKE UP IS TWO 200 AMP SERVICE DISCONNECTS. THE VIOLATIONS ARE AS FOLLOWS: NO ACCESS TO SERVICE DISCONNECTS, USED OPENINGS, NO LABELING.

ELECTRICAL VIOLATIONS
BELOW ARE THE PEDESTAL / DISCONNECTING MEANS VIOLATIONS

UNIT 1 PEDESTAL
UNUSED OPENINGS
NO LABELING

UNIT 2 PEDESTAL
OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION)
UNUSED OPENINGS
NO LABELING

UNIT 3 PEDESTAL
OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION)
NO LABELING

UNIT 4 PEDESTAL
OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION)
NO LABELING

UNIT 5 PEDESTAL
UNUSED OPENINGS
THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS
NO LABELING

UNIT 6 PEDESTAL
NO LABELING

UNIT 7 PEDESTAL
UNUSED OPENINGS
UNABLE TO DETERMINE BREAKER AMPACITY
NO LABELING

UNIT 8 PEDESTAL
THE MAIN BREAKER IS 100 AMPS, THE POWER SUPPLY CORD IS RATED FOR 50 AMPS.
THE BREAKER IS NOT PROPERLY SEATED
UNUSED OPENINGS
NO LABELING

UNIT 9 PEDESTAL
UNUSED OPENINGS
NO LABELING

UNIT 10 PEDESTAL
UNUSED OPENINGS
THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS
NO LABELING

UNIT 11 PEDESTAL
NO LABELING

UNIT 12 PEDESTAL
OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION)
UNUSED OPENINGS
THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS
NO LABELING

UNIT 13 PEDESTAL
OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION)
UNUSED OPENINGS
NO LABELING
THE MAIN BREAKER CONSIST OF TWO 30 AMP SINGLE POLE TYPE BREAKERS WITH NO HANDLE TIE

UNIT 14 PEDESTAL
OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION)
THE MAIN BREAKER IS 50 AMPS, THE POWER SUPPLY CORD IS RATED FOR 30 AMPS
NO LABELING

UNIT 16 PEDESTAL
NO LABELING
THE POWER SUPPLY CORD HAS MISSING INSULATION AND THE CONDUCTORS HAVE TAPE AT THE ENDS.

UNIT 17 PEDESTAL
UNUSED OPENINGS
THE POWER SUPPLY CORD HAS MISSING INSULATION AND THE CONDUCTORS HAVE TAPE AT THE ENDS.
NO LABELING

UNIT 18 PEDESTAL
THE RECEPTACLE TO THE MAIN BREAKER IS NOT PROPERLY SEATED.
NO LABELING

UNIT 19 PEDESTAL
UNUSED OPENINGS
THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS
NO LABELING



UNIT 20 PEDESTAL
UNUSED OPENINGS
UNABLE TO DETERMINE BREAKER AMPACITY
NO LABELING

UNIT 22 PEDESTAL
THE MAIN BREAKER IS 50 AMPS, THE POWER SUPPLY CORD IS RATED FOR 30 AMPS
UNUSED OPENINGS
NO LABELING

UNIT 23 PEDESTAL
NO LABELING

UNIT 24 PEDESTAL
NO LABELING
UNUSED OPENINGS

UNIT 25 PEDESTAL
NO LABELING
UNUSED OPENINGS

UNIT 26 PEDESTAL
NO LABELING

UNIT 27 PEDESTAL
NO LABELING
MISSING DEAD FRONT

UNIT 28 PEDESTAL
EXPOSED CONDUCTORS
MISSING PEDESTAL LOWER COVER
NO LABELING

UNIT 29 PEDESTAL
NO LABELING
MISSING DEAD FRONT

UNIT 30 (HOUSE)
NO LABELING

UNIT 32 PEDESTAL
NO LABELING
UNUSED OPENINGS
CLEARANCE IS OBSTRUCTED BY SEWER PIPE (WITHIN THE 36 INCHES)

UNIT 33 PEDESTAL
NO LABELING
UNUSED OPENINGS
UNAPPROVED POWER SUPPLY CORD (UF CABLE BEING USED AS POWER SUPPLY CORD)
PEDESTAL IS NOT PROPERLY SUPPORT
PEDESTAL HAS MISSING HARDWARE
THE MAIN BREAKER CONSIST OF TWO 20 AMP SINGLE POLE TYPE BREAKERS WITH NO HANDLE TIE

UNIT 34 PEDESTAL
NO LABELING
UNUSED OPENINGS
OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION)
PEDESTAL HE MISSING HARDWARE

UNIT 35 PEDESTAL
NO LABELING

UNIT 36 PEDESTAL
OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION)
NO LABELING
UNUSED OPENINGS
CLEARANCE IS OBSTRUCTED BY FENCE AND MATERIAL
NON METALLIC SHEATHED CABLE IS BEING USED AS A SUPPLY CORD.
THERE IS BROKEN A RECEPTACLE
THE RECEPTACLE BEING USED IS IMPROPER.

UNIT 37 PEDESTAL
NO LABELING

UNIT 38 PEDESTAL
NO LABELING
CLEARANCE IS OBSTRUCTED BY HOSE AND MISCELLANEOUS EQUIPMENT

UNIT 39 PEDESTAL
NO LABELING

UNIT 40 PEDESTAL
NO LABELING
UNUSED OPENINGS
THE MAIN BREAKER IS 60 AMPS, THE POWER SUPPLY CORD IS RATED FOR 50 AMPS

UNIT 41 PEDESTAL
NO LABELING
UNUSED OPENINGS

UNIT 42 PEDESTAL
NO LABELING
UNUSED OPENINGS
PEDESTAL HAS MISSING HARDWARE
UNABLE TO DETERMINE BREAKER AMPACITY


UNIT 43 PEDESTAL
NO LABELING
UNUSED OPENINGS
PEDESTAL HAS MISSING HARDWARE
THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS

UNIT 44 PEDESTAL
NO LABELING
EXTENSION CORDS ARE BEING USED EMPLACE OF A POWER SUPPLY CORD

UNIT 45 PEDESTAL
NO LABELING
UNUSED OPENINGS
UNAPPROVED POWER SUPPLY CORD (UNPROTECTED CABLE BEING USED AS POWER SUPPLY CORD)

UNIT 46 PEDESTAL
MISSING PEDESTAL HARDWARE
NO DEAD FRONT
NO LABELING
UNUSED OPENINGS

UNIT 47 PEDESTAL
NO LABELING

UNIT 48 PEDESTAL
NO LABELING
UNUSED OPENINGS
THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS

UNIT 49 PEDESTAL
NO LABELING
UNUSED OPENINGS
THE MAIN BREAKER IS 100 AMPS, THE POWER SUPPLY CORD IS RATED FOR 50 AMPS

UNIT 50 PEDESTAL
NO LABELING

UNIT 51 PEDESTAL
NO LABELING
CLEARANCE IS OBSTRUCTED BY FENCE.
OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION)

UNIT 52 PEDESTAL
OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION)
NO LABELING
NO DEAD FRONT
UNUSED OPENINGS


UNIT 53 PEDESTAL
NO LABELING
PEDESTAL HE MISSING HARDWARE

UNIT 54 PEDESTAL
CLEARANCE IS OBSTRUCTED BY FENCE
UNUSED OPENINGS
NO LABELING
POWER SUPPLY CORD IS CONNECT DIRECT TO THE METER ( NO OVER CURRENT PROTECTION)

UNIT 55 PEDESTAL
THE MAIN BREAKER IS 50 AMPS, THE POWER SUPPLY CORD IS RATED FOR 40 AMPS
UNUSED OPENINGS
NO LABELING
FASTENERS ARE MISSING TO THE DUAL PEDESTAL HARDWARE.

UNIT 56 PEDESTAL
UNABLE TO DETERMINE BREAKER AMPACITY
OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION)
CLEARANCE IS OBSTRUCTED BY FENCE.
PEDESTAL HAS MISSING HARDWARE
UNUSED OPENINGS
NO LABELING

UNIT 57 PEDESTAL
UNUSED OPENINGS
NO LABELING
THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS
PVC CONDUIT IS NOT CONTINUOUS.

UNIT 58 PEDESTAL
NO LABELING



UNIT 59 PEDESTAL
CLEARANCE IS OBSTRUCTED BY FENCE.
OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION)
PEDESTAL BREAKER NOT PROPERLY SEATED (UNABLE TO SHUT OFF)

UNIT 60 PEDESTAL
NO LABELING
OCCUPANT HAS NO ACCESS TO THE PEDESTAL (OVER CURRENT PROTECTION)