Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
Case Number - T14DV00449
Inspection Description - INSP - FOLLOW UP CODE ENFORCE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2014 | INSP - FOLLOW UP CODE ENFORCE | Approved | Site review with owner, electrician, I.Stevens and myself; compliant; permit T14CM07610 finaled; grounding of boxes included. | |
| 10/09/2014 | INSP - FOLLOW UP CODE ENFORCE | Approved | Site inspection with owner and engineer. Reviewed proposals. | |
| 08/06/2014 | INSP - FOLLOW UP CODE ENFORCE | Approved | Inspection conducted at panelboard including Inspector Stevens, Vidal, and myself. All subpanels were numbered; rotted support beams were replaced with steel; rusted and peeling portions were cleaned and painted; grounding wire connections cleaned; dead fronts added to subpanels; 5'0 wood panel fencing securely installed with a padlocked door on east end clearly marked as electrical; ramada added to top to shield from elements; another door is present at west end that can be opened only from inside with deadbolt; meter base for unit #35 previously installed without permit had a finaled permit on file with approved inspection. Items that will need to be changed: the gauge of metal on the deadfronts need to be the same as the cover (heavier); rivets used to install deadfronts will need to be replaced with appropriate screws allowing removal of deadfronts if necessary; one set of grounding wires on north side of panelboard needs to have more paint removed from connection points. A signed review from a licensed electrician confirming good operating condition of entire subpanel will be the final item required. | |
| 07/07/2014 | INSP - FOLLOW UP CODE ENFORCE | Approved | Met owner at location w/ electrical engineer to review area of required repair. | |
| 06/26/2014 | INSP - FOLLOW UP CODE ENFORCE | Approved | No change; permit still in issued status. | |
| 05/21/2014 | INSP - FOLLOW UP CODE ENFORCE | Approved | Permit T14CM02875 in applied status. | |
| 01/23/2014 | INSP - FOLLOW UP CODE ENFORCE | Approved | Confirmed junction boxes are secured with padlocks. | |
| 01/22/2014 | INSP - FOLLOW UP CODE ENFORCE | Approved | Electrical equipment located on a mounting board south of Unit A that includes several (approx. 16) service panels for individual units was inspected. Inspectors Pumphrey, Stevens, and Hollander present along with PM Carlos and RPM Electric. The panels and mounting board were found to be deteriorated due to age and weather dilapidation with the exterior and interior of the metal panels exhibiting degradation due to rust and water damage; the wood supports have considerable termite damage and are loose; the wood is no longer weather proof and has evidence of deterioration. The equipment on the interior of the panels have been modified over time from the original installation, with modifications not installed under permit, rated for exterior use, or to adopted code at time of installation; some of the equipment is not rated for exterior use. The aged and modified equipment, as installed, does not allow for installation of a proper dead front. Electrical equipment and main disconnect area located on the south side of the building at Unit B lacks appropriate clearance in front of equipment due to the storage, debris, and vegetation impeding access. The service panel for Unit B is missing dead front. The older sub-panel housing breakers under the main disconnect is also missing dead front and has spliced conductors that exceed the maximum allowable space at the bottom of the panel. The yard at Unit B (Manager's unit) has a large accumulation of refuse and vegetation over 6"; dogs and dog waste are also present in this area) |