Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2014 | INSP - INITIAL CODE ENFORCMENT | Approved | THE MAIN DISCONNECT HAS A PAD LOCK AND THE OWNER IS UNABLE TO OPEN. I DID SEE THE GROUNDING ELECTRODE CONDUCTOR HAS BEEN CUT. THERE IS A INDOOR TYPE JUNCTION BOX WITH A RECEPTACLE ABUTTING THE MAIN DISCONNECT OUTDOOR LOCATION. THE BACKER BOARD TO THE DISCONNECT IS DETERIORATED. THE INTERIOR PANEL BOARD HAS IMPROPER LABELING. VERIFY THE NEW CIRCUITS AND LOADS THAT WERE INSTALLED AND SUPPLYING POWER TO THE FISH TANKS AND EQUIPMENT. THE ELECTRICAL METALLIC TUBING FROM THE CEILING IS NOT INSTALLED OR SUPPORTED PROPERLY. |